{"product_id":"ic698cre040-ge-fanuc-rx7i-pacsystems-cpu-module","title":"GE Fanuc IC698CRE040 PACSystems Rx7i CPU Module","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\u003cp\u003eThe IC698CRE040 is a high-performance Central Processing Unit (CPU) module designed for the GE Fanuc PACSystems Rx7i control platform. Built around a 1.8 GHz Pentium M processor, this module serves as the primary controller for demanding industrial applications, including power generation, oil and gas processing, and large-scale manufacturing. It is engineered to handle complex logic, motion control, and high-speed data processing while maintaining low latency to maximize system uptime in critical distributed control environments.\u003c\/p\u003e\u003ch3\u003eFeatures\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eEquipped with a 1.8 GHz Pentium M processor for high-speed logic execution.\u003c\/li\u003e\n\u003cli\u003eIncludes 64 MB of user memory for extensive program storage and data logging.\u003c\/li\u003e\n\u003cli\u003eDual RJ45 Ethernet ports supporting 10\/100 Mbps auto-negotiation and EGD (Ethernet Global Data) communication.\u003c\/li\u003e\n\u003cli\u003eDual serial interfaces supporting RS-232 and RS-485 protocols for legacy device connectivity.\u003c\/li\u003e\n\u003cli\u003eSupports up to 16 simultaneous web and FTP connections for real-time monitoring.\u003c\/li\u003e\n\u003cli\u003eHigh-precision internal timing with minimal drift for synchronized operation in redundant systems.\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eApplications\u003c\/h3\u003e\u003cp\u003eThis CPU module is suitable for use in high-availability industrial automation systems, including:\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eLarge-scale power generation facilities.\u003c\/li\u003e\n\u003cli\u003eOil refining and petrochemical processing plants.\u003c\/li\u003e\n\u003cli\u003eDeep-pit mining operations requiring robust motion and logic control.\u003c\/li\u003e\n\u003cli\u003eDistributed control systems (DCS) requiring multi-protocol communication.\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\u003ctable border=\"1\"\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC698CRE040\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProcessor\u003c\/td\u003e\n\u003ctd\u003ePentium M 1.8 GHz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUser Memory\u003c\/td\u003e\n\u003ctd\u003e64 MB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEthernet Ports\u003c\/td\u003e\n\u003ctd\u003e2 x RJ45 (10\/100 Mbps)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSerial Ports\u003c\/td\u003e\n\u003ctd\u003e2 x RS-232 \/ RS-485\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Requirements\u003c\/td\u003e\n\u003ctd\u003e5 VDC (6.8 A), +\/- 12 VDC (0.003 A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e34 W (Nominal)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 degC (32 to 140 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTiming Accuracy\u003c\/td\u003e\n\u003ctd\u003e+\/- 0.01 percent\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eEnsure the PACSystems Rx7i rack is powered down before inserting or removing the CPU module to prevent electrical damage.\u003c\/li\u003e\n\u003cli\u003eHandle the module using proper ESD (electrostatic discharge) precautions to protect internal circuitry.\u003c\/li\u003e\n\u003cli\u003eEnsure the module is fully seated in the designated slot and secured with the integrated locking mechanism.\u003c\/li\u003e\n\u003cli\u003eRoute communication cables away from high-voltage power lines and sources of electromagnetic interference (EMI) to maintain signal integrity.\u003c\/li\u003e\n\u003cli\u003eVerify that the ventilation path is clear to allow for proper heat dissipation within the operating temperature range.\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eFAQ\u003c\/h3\u003e\u003ch3\u003eWhat is the primary function of the IC698CRE040?\u003c\/h3\u003e\u003cp\u003eThe IC698CRE040 acts as the central processor for the PACSystems Rx7i system, managing logic execution, data logging, and communication between field devices and the control network.\u003c\/p\u003e\u003ch3\u003eDoes this module support redundant configurations?\u003c\/h3\u003e\u003cp\u003eYes, the module is designed to support synchronized operation, making it suitable for redundant system architectures where high availability is required.\u003c\/p\u003e\u003ch3\u003eWhat type of memory does this CPU utilize?\u003c\/h3\u003e\u003cp\u003eThe module features 64 MB of user memory, which is utilized for storing logic programs, configuration data, and system logs.\u003c\/p\u003e","brand":"GE FANUC","offers":[{"title":"Default Title","offer_id":50730341826812,"sku":"IC698CRE040","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0787\/9983\/1292\/files\/wm_1_c1813ca2-4844-4062-9357-4eb0b1f56102.jpg?v=1785217820","url":"https:\/\/www.electronicplc.com\/ar\/products\/ic698cre040-ge-fanuc-rx7i-pacsystems-cpu-module","provider":"Electronic PLC","version":"1.0","type":"link"}