{"product_id":"siemens-6es7315-2eh13-0ab0-simatic-s7-300-cpu-315-2-pn-dp","title":"Siemens 6ES7315-2EH13-0AB0 SIMATIC S7-300 CPU 315-2 PN\/DP","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\u003cp\u003eThe Siemens 6ES7315-2EH13-0AB0 is a high-performance Central Processing Unit (CPU) designed for the SIMATIC S7-300 automation system. This CPU 315-2 PN\/DP module provides robust processing power for medium-to-large scale industrial control applications. It features 256 KB of integrated working memory and supports dual-interface communication, allowing for seamless integration into complex network architectures. Please note that this specific model has been superseded by the 6ES7315-2EH14-0AB0.\u003c\/p\u003e\u003ch3\u003eFeatures\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eIntegrated 256 KB working memory for program and data storage.\u003c\/li\u003e\n\u003cli\u003eDual interface capability: MPI\/DP (up to 12 Mbit\/s) and Ethernet PROFINET.\u003c\/li\u003e\n\u003cli\u003eRequires a Micro Memory Card (MMC) for operation.\u003c\/li\u003e\n\u003cli\u003eSupports advanced industrial communication protocols for distributed I\/O and HMI connectivity.\u003c\/li\u003e\n\u003cli\u003eCompact design suitable for standard S7-300 rail mounting.\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eApplications\u003c\/h3\u003e\u003cp\u003eThis CPU is widely utilized in manufacturing, process automation, and infrastructure control systems where reliable PLC performance and PROFINET connectivity are required. It is ideal for managing distributed I\/O stations, motion control tasks, and data exchange between plant-floor controllers and higher-level management systems.\u003c\/p\u003e\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\u003ctable border=\"1\"\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Model\u003c\/td\u003e\n\u003ctd\u003e6ES7315-2EH13-0AB0\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCPU Type\u003c\/td\u003e\n\u003ctd\u003eCPU 315-2 PN\/DP\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWorking Memory\u003c\/td\u003e\n\u003ctd\u003e256 KB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC (20.4 V to 28.8 V range)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e650 mA (rated), 100 mA (no-load)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Loss\u003c\/td\u003e\n\u003ctd\u003e3.5 W (typical)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInrush Current\u003c\/td\u003e\n\u003ctd\u003e2.5 A (typical)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Interfaces\u003c\/td\u003e\n\u003ctd\u003eMPI\/DP (12 Mbit\/s), PROFINET\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHardware Version\u003c\/td\u003e\n\u003ctd\u003e01\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFirmware Version\u003c\/td\u003e\n\u003ctd\u003eV2.6\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProgramming Software\u003c\/td\u003e\n\u003ctd\u003eSTEP 7 V5.4 SP2 or higher\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eEnsure the CPU is mounted on a standard 35mm DIN rail and secured properly within the S7-300 rack.\u003c\/li\u003e\n\u003cli\u003eAlways power down the system before inserting or removing the CPU or any communication modules to prevent electrical arcing or damage to the backplane.\u003c\/li\u003e\n\u003cli\u003eUse shielded cables for PROFINET and PROFIBUS connections to minimize EMI interference in industrial environments.\u003c\/li\u003e\n\u003cli\u003eEnsure the 24V DC power supply is protected by a minimum 2A external fuse.\u003c\/li\u003e\n\u003cli\u003eHandle the module using ESD-safe practices to prevent damage to sensitive internal components.\u003c\/li\u003e\n\u003cli\u003eVerify that the required Micro Memory Card is correctly inserted before attempting to power up the unit.\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eFAQ\u003c\/h3\u003e\u003ch3\u003eIs this CPU still the current production model?\u003c\/h3\u003e\u003cp\u003eNo, the 6ES7315-2EH13-0AB0 has been officially replaced by the 6ES7315-2EH14-0AB0. This unit is typically sourced as a spare or for maintenance of existing legacy installations.\u003c\/p\u003e\u003ch3\u003eWhat programming software is required for this module?\u003c\/h3\u003e\u003cp\u003eThis CPU requires Siemens STEP 7 V5.4 SP2 or higher for configuration and programming.\u003c\/p\u003e\u003ch3\u003eDoes this unit include a memory card?\u003c\/h3\u003e\u003cp\u003eNo, a Micro Memory Card (MMC) is required for operation but is not typically included with the CPU module itself. Please ensure you have a compatible MMC available for your project.\u003c\/p\u003e","brand":"Siemens","offers":[{"title":"Default Title","offer_id":50743437689084,"sku":"6ES7315-2EH13-0AB0","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0787\/9983\/1292\/files\/wm_1_c1a2759f-42b6-4626-a289-ce068d961fe0.jpg?v=1785469412","url":"https:\/\/www.electronicplc.com\/ar\/products\/siemens-6es7315-2eh13-0ab0-simatic-s7-300-cpu-315-2-pn-dp","provider":"Electronic PLC","version":"1.0","type":"link"}