{"product_id":"mric-32-24vdc-dps-relay-output-module-yokogawa","title":"MRIC-32\/24VDC\/DPS Relay Output Module Yokogawa","description":"\u003cp\u003eThe \u003cstrong\u003eYokogawa MRIC-32\/24VDC\/DPS\u003c\/strong\u003e serves as the primary \u003cstrong\u003eMRIC-32\/24VDC\/DPS\u003c\/strong\u003e Relay Output Module utilized to execute discrete switching operations across distributed control system platforms.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eMRIC-32\/24VDC\/DPS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eYokogawa\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eJapan\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.6 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e3.5 cm x 15.0 cm x 13.0 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to 50 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e24 VDC, 0.5 A max\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Channels\u003c\/td\u003e\n\u003ctd\u003e32-channel relay output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eChannel-to-Channel Isolation and Loop Protocol\u003c\/h3\u003e\n\u003cp\u003eThe hardware configuration maintains strict electrical isolation across output switching channels to eliminate ground loop interference and suppress transient voltage spikes from inductive field loads. Integration with standard process control communication protocols ensures continuous diagnostic feedback, channel status verification, and transparent digital command execution without degrading contact lifespan.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What are the restrictions regarding hot-swapping the MRIC-32\/24VDC\/DPS module?\u003c\/p\u003e\n\u003cp\u003eA: Hot-swapping is restricted unless explicit system redundancy configurations or maintenance bypass modes are active to prevent unintended field actuator states.\u003c\/p\u003e\n\u003cp\u003eQ: How are inductive loads handled on the relay output channels?\u003c\/p\u003e\n\u003cp\u003eA: External suppression diodes or RC snubber networks must be installed across inductive loads to protect relay contacts from high-voltage transient arcs during de-energization.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eMount the unit directly into the designated slot of the node base, ensuring physical alignment with backplane connectors before engaging securing screws. Route field wiring away from high-voltage power conduits and use shielded cables for control signals to maintain electromagnetic compatibility. Terminate cable shielding and ground drain wires securely to the designated cabinet earth grounding bar.\u003c\/p\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":50364009152764,"sku":"MRIC-32\/24VDC\/DPS","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0787\/9983\/1292\/files\/MRIC-3224VDCDPS2.jpg?v=1784597681","url":"https:\/\/www.electronicplc.com\/es\/products\/mric-32-24vdc-dps-relay-output-module-yokogawa","provider":"Electronic PLC","version":"1.0","type":"link"}