{"product_id":"experion-analog-input-module-honeywell-tc-iah061-96978074-a01","title":"Experion Analog Input Module Honeywell TC-IAH061 96978074-A01","description":"\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003eThe Honeywell TC-IAH061 is a high-precision analog input module for the Experion Series-A I\/O system. It acquires signals from field transmitters and sensors, converting process variables into digital data for the controller. With six galvanically isolated channels, the module supports both voltage and current inputs, enabling flexible and reliable signal integration in industrial environments.\u003c\/p\u003e\n\u003chr\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eDetails\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel Number\u003c\/td\u003e\n\u003ctd\u003eTC-IAH061\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e96978074-A01\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCondition\u003c\/td\u003e\n\u003ctd\u003e100% Brand New Original\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e6 (Galvanically Isolated)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage Range\u003c\/td\u003e\n\u003ctd\u003e±10.5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current Range\u003c\/td\u003e\n\u003ctd\u003e0–21 mA (via 249Ω resistor)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Resolution\u003c\/td\u003e\n\u003ctd\u003e343 µV (typical)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Resolution\u003c\/td\u003e\n\u003ctd\u003e0.34 µA (typical)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eExperion PKS Series-A I\/O\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003chr\u003e\n\u003ch3\u003eEngineering Advantages\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eFlexible Input Configuration\u003c\/strong\u003e\u003cbr\u003eSupports both voltage and current signals on a per-channel basis, reducing spare part requirements.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eHigh Noise Immunity\u003c\/strong\u003e\u003cbr\u003eFull galvanic isolation eliminates ground loops and improves signal accuracy in noisy environments.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003ePrecision Measurement\u003c\/strong\u003e\u003cbr\u003eFine resolution enables accurate monitoring for critical applications such as flow, pressure, and leak detection.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eStreamlined Integration\u003c\/strong\u003e\u003cbr\u003eDirect backplane compatibility simplifies wiring and installation for field instruments.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003chr\u003e\n\u003ch3\u003eFAQs\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eIs this TC-IAH061 a genuine Honeywell product?\u003c\/strong\u003e\u003cbr\u003eYes, it is supplied as 100% brand new, original hardware with verified part number and factory packaging.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eDoes it require external resistors for current inputs?\u003c\/strong\u003e\u003cbr\u003eYes, a 249Ω precision resistor is required to convert current signals into measurable voltage.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eCan voltage and current signals be mixed?\u003c\/strong\u003e\u003cbr\u003eYes, each channel can be configured independently to accept different signal types.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eHow does galvanic isolation improve system reliability?\u003c\/strong\u003e\u003cbr\u003eIt prevents electrical faults or surges from propagating between channels or to the controller, ensuring stable operation.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":48907701092604,"sku":"TC-IAH061 96978074-A01","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0787\/9983\/1292\/files\/TC-IAH061_96978074-A01.jpg?v=1775027466","url":"https:\/\/www.electronicplc.com\/products\/experion-analog-input-module-honeywell-tc-iah061-96978074-a01","provider":"Electronic PLC","version":"1.0","type":"link"}