{"product_id":"honeywell-cc-tfb402-experion-pks-fieldbus-interface-iota-module","title":"HONEYWELL CC-TFB402 Experion PKS Fieldbus Interface IOTA Module","description":"\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003eThe Honeywell CC-TFB402 (Part Number: 51308309-275 Rev E) is a specialized Input\/Output Termination Assembly (IOTA) used within the Experion PKS architecture for Fieldbus Interface Modules. It provides the physical interface for up to four independent Fieldbus segments, enabling high-speed, bidirectional communication between the C300 controller and smart field devices. Supporting both FOUNDATION Fieldbus and Profibus protocols, this board ensures reliable data transmission in industrial environments. The unit is supplied as 100% Brand New Original and features conformal coating for enhanced durability in harsh conditions.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eDetails\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel Number\u003c\/td\u003e\n\u003ctd\u003eCC-TFB402\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork Ports\u003c\/td\u003e\n\u003ctd\u003e4 Independent Fieldbus Connections\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported Protocols\u003c\/td\u003e\n\u003ctd\u003eFOUNDATION Fieldbus, Profibus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-20°C to +60°C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e170 mm × 120 mm × 40 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.75 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection\u003c\/td\u003e\n\u003ctd\u003eConformal Coating (Standard)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eEngineering Advantages\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eOptimized Signal Integrity:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003ePrecision trace design and high-quality termination minimize signal reflections, ensuring stable communication over long distances.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eRedundancy and Fault Tolerance:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eSupports redundant configurations to maintain connectivity even if one module fails.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eHarsh Environment Readiness:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eConformal coating protects against moisture, dust, and chemical exposure in demanding industrial settings.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eSimplified Network Scalability:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eFour independent segments allow organized expansion without impacting other fieldbus networks.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFAQs\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eDoes the CC-TFB402 include the Fieldbus Interface Module (FIM)?\u003c\/strong\u003e\u003cbr\u003eNo, it is only the termination assembly (IOTA). The Fieldbus Interface Module must be installed separately.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eIs it compatible with DIN rail mounting?\u003c\/strong\u003e\u003cbr\u003eYes, it supports DIN rail mounting as well as direct panel installation for high-vibration environments.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eWhat improvements does Revision E provide?\u003c\/strong\u003e\u003cbr\u003eRevision E includes updated internal components and enhanced conformal coating for improved reliability and compliance.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eDoes it supply power to fieldbus devices?\u003c\/strong\u003e\u003cbr\u003eNo, it handles signal routing only. An external Fieldbus power supply is required to energize FOUNDATION Fieldbus segments.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":48949973352700,"sku":"CC-TFB402","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0787\/9983\/1292\/files\/CC-TFB402.jpg?v=1775723087","url":"https:\/\/www.electronicplc.com\/products\/honeywell-cc-tfb402-experion-pks-fieldbus-interface-iota-module","provider":"Electronic PLC","version":"1.0","type":"link"}