{"product_id":"woodward-9905-001k-spm-a-digital-synchronizer","title":"Woodward 9905-001K SPM-A Digital Synchronizer","description":"\u003cp\u003eConfigured for frequency and phase matching in generator control networks, the \u003cstrong\u003eWoodward 9905-001K\u003c\/strong\u003e (\u003cstrong\u003eSPM-A\u003c\/strong\u003e Digital Synchronizer) provides direct physical\/electrical execution. The unit continuously monitors the voltage, frequency, and phase relationships between an offline generator and a live busbar or target generator. Upon achieving alignment within defined thresholds, it issues a discrete breaker close command to enable parallel bus connection without current surges or mechanical shaft stress.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e9905-001K\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eWoodward\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eSPM-A Synchronizer\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e115 VAC RMS or 230 VAC RMS (+\/-10%)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFrequency Range\u003c\/td\u003e\n\u003ctd\u003e50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePhase Angle Tolerance\u003c\/td\u003e\n\u003ctd\u003e+\/-10 deg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e5 W maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Options\u003c\/td\u003e\n\u003ctd\u003eHigh\/Low impedance, EPG compatible\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e15.8 x 15.8 x 4 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.69 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003ePanel-mounted\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVibration Tolerance\u003c\/td\u003e\n\u003ctd\u003e1 mm (2-13.2 Hz), 0.7 g (13.2-150 Hz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShock Resistance\u003c\/td\u003e\n\u003ctd\u003e10 g, 1\/2 sine wave, 11 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eActuator Loop Feedback Response \u0026amp; Phase Matching\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eWoodward 9905-001K\u003c\/strong\u003e integrates direct analog interface circuitry to evaluate potential transformer (PT) signal inputs from both generator and bus sources. Its internal discriminator computes phase angle error and velocity differentials to optimize actuator loop feedback response. Speed adjustment signals are output directly to compatible speed controls, such as EPG series governors, adjusting prime mover speed to achieve dynamic synchronization prior to breaker closure.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How is input voltage selection configured on the Woodward 9905-001K unit?\u003c\/p\u003e\n\u003cp\u003eA: Terminal jumper arrangements allow selection between 115 VAC RMS and 230 VAC RMS potential transformer operating ranges within a +\/-10% tolerance band.\u003c\/p\u003e\n\u003cp\u003eQ: What output modes are supported for interface with prime mover governors?\u003c\/p\u003e\n\u003cp\u003eA: The device provides discrete high-impedance, low-impedance, and EPG-compatible output configurations to interface directly with dynamic speed control loops.\u003c\/p\u003e\n\u003cp\u003eQ: What are the physical mounting orientation requirements for shock and vibration compliance?\u003c\/p\u003e\n\u003cp\u003eA: The module must be rigidly fastened via its panel-mount chassis cutout to ensure vibration attenuation up to 0.7 g across the 13.2 Hz to 150 Hz spectrum.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eEnsure power and sensing lines are disconnected before landing wires on terminal blocks.\u003c\/li\u003e\n\u003cli\u003eRoute potential transformer (PT) reference wiring in dedicated shielded twisted-pair cables separate from high-voltage AC power lines.\u003c\/li\u003e\n\u003cli\u003eEarth ground the cable shields at the panel entry point to prevent common-mode noise interference on sensing inputs.\u003c\/li\u003e\n\u003cli\u003eMaintain a minimum 5-turn thread engagement when torquing panel mounting hardware.\u003c\/li\u003e\n\u003cli\u003eVerify that terminal voltage tap jumpers match the system sensing level (115 VAC RMS or 230 VAC RMS) prior to energizing the module.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Woodward","offers":[{"title":"Default Title","offer_id":50743033004284,"sku":"9905-001K","price":120.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0787\/9983\/1292\/files\/9905-001K1.jpg?v=1785464630","url":"https:\/\/www.electronicplc.com\/products\/woodward-9905-001k-spm-a-digital-synchronizer","provider":"Electronic PLC","version":"1.0","type":"link"}