قطع غيار أصلية للأتمتة | توصيل سريع عالمي | ضمان لمدة 12 شهرًا — [احصل على عرض سعر]

The Schneider Electric ASB817116 (AS-B817-116) is a robust 16-channel digital input module designed for integration within the Modicon 800 Series I/O architecture. This module is specifically engineered to interface with 115 VAC discrete field signals, making it a reliable solution for monitoring status from motor starters, limit switches, and proximity sensors in industrial environments. By utilizing internal RC filtering and optical isolation, the module effectively manages high-voltage signals while protecting the controller backplane from electrical transients and potential ground loops.
This module is widely deployed in demanding industrial sectors, including power utility generation, chemical processing, oil and gas refining, and heavy-duty mining. Its ability to handle line-voltage signals directly allows for simplified circuit design in applications where monitoring safety interlocks and motor control center (MCC) states is critical.
| Model | ASB817116 |
| Channels | 16 Discrete Inputs |
| Input Voltage | 115 VAC Nominal (85-130 VAC Range) |
| Frequency | 47 to 63 Hz |
| ON-State Threshold | 85 VAC Minimum |
| OFF-State Threshold | 40 VAC Maximum |
| Input Impedance | 12 kOhm at 60 Hz |
| Isolation | 1500 VAC (Channel-to-Bus) |
| Backplane Current | 250 mA at 5 VDC |
| Operating Temperature | 0 to 60 deg C |
| Storage Temperature | -40 to 85 deg C |
| Humidity | 5 to 95% non-condensing |
What is the primary function of the ASB817116?
This module serves as a digital input interface that converts 115 VAC field signals into logic levels compatible with the Modicon 800 Series controller backplane.
Does this module require external power?
The module draws its internal logic power (250 mA at 5 VDC) directly from the chassis backplane, while the inputs are powered by the 115 VAC field signal source.
How are the channels isolated?
The module uses optical isolators for each channel, providing a 1500 VAC barrier that protects the internal controller logic from field-side voltage spikes.