The Allen-Bradley 1746-OW16 is a high-performance 16-point digital output module designed for the SLC 500 programmable logic controller (PLC) system. This module features electromechanical relay contacts, providing robust isolation and...

15 la gente está viendo esto ahora mismo

DisponibilidadBajas existencias: quedan 2

SKU: 1746-OW16
Proveedora: Allen-Bradley

Envíos y devoluciones

Entrega confiable a nivel mundial

  • Transportistas: Envíos a través de DHL, FedEx, UPS o USPS .
  • Envío: Los pedidos se procesan en 1-2 días hábiles y se envían dentro de 3-5 días hábiles .
  • Seguimiento: Detalles completos de seguimiento proporcionados por correo electrónico después del envío.

Garantía de devolución de dinero de 30 días

  • Garantía: período de devolución de 30 días para productos en stock y sellados de fábrica.
  • Condición: Los artículos deben estar sin abrir, sin usar y en su embalaje original.
  • Autenticidad: Garantizamos hardware 100% original y auténtico.

¿Necesitas más información? Consulta nuestra Política de envíos y reembolsos completa.

Autenticidad y garantía

  • Garantía genuina: Suministramos únicamente piezas de automatización industrial 100% originales, nuevas y selladas de fábrica .
  • Cobertura total: cada componente está respaldado por una garantía integral de 12 meses a partir de la fecha de compra.
  • Trazabilidad: Todos los productos se entregan con documentación original de fábrica y accesorios para un pleno cumplimiento industrial.

Soporte técnico y abastecimiento

  • Asistencia de expertos: Nuestro equipo técnico ofrece consulta gratuita para ayudarle a verificar la compatibilidad de los sistemas DCS y PLC.
  • Abastecimiento de piezas raras: nos especializamos en componentes obsoletos y difíciles de encontrar de Allen-Bradley, Siemens, ABB, HIMA y más.
  • Consultas al por mayor: contáctenos en pambo@5gplc.com para obtener precios por volumen o cotizaciones de proyectos personalizados.
Ver todos los detalles

Description

The Allen-Bradley 1746-OW16 is a high-performance 16-point digital output module designed for the SLC 500 programmable logic controller (PLC) system. This module features electromechanical relay contacts, providing robust isolation and the ability to switch a wide range of AC and DC voltages. With its 16 outputs divided into two isolated groups of eight, it offers significant flexibility for complex control applications, allowing users to manage different voltage types simultaneously without the need for external interposing relays.

Features

  • 16 normally open (N.O.) relay contact outputs.
  • Two isolated groups of 8 points each, allowing for mixed-voltage operation (AC and DC).
  • Wide operating voltage range: 5 to 265V AC and 5 to 125V DC.
  • Removable terminal block for simplified field wiring and maintenance.
  • Front-panel LED status indicators for quick diagnostic monitoring.
  • Dry contact design eliminates the need for intermediary relay circuitry in many applications.

Applications

  • Manufacturing and machine automation, including assembly lines and conveyors.
  • Water and wastewater processing for control of dosing pumps, valves, and mixers.
  • Food, beverage, and packaging equipment such as sorting gates and sealers.
  • Building automation systems for lighting, HVAC, and damper control.
  • Heavy industrial loops requiring relay isolation.

Technical Specifications

Model 1746-OW16
Manufacturer Allen-Bradley (Rockwell Automation)
Output Type Electromechanical Relay (N.O.)
Number of Outputs 16
Points per Common 8
Operating Voltage 5 to 265V AC / 5 to 125V DC
Min. Load Current 10 mA @ 5V DC
Operating Temperature 0 to 60 degC (32 to 140 degF)
Storage Temperature -40 to 85 degC (-40 to 185 degF)
Operating Humidity 5 to 95% (non-condensing)

Installation Guidelines

  • Slot Selection: The 1746-OW16 can be installed in any available I/O slot of an SLC 500 chassis. Note that Slot 0 is reserved for the processor or remote I/O adapter.
  • Handling: Always power down the chassis before inserting or removing any I/O module to prevent electrical damage or system faults.
  • Mounting: Align the module's circuit board with the chassis card guides. Slide the module in until the top and bottom locking tabs snap securely into place.
  • Wiring: Ensure external fusing is installed for each output to protect the relay contacts from overcurrent or short-circuit conditions, as the module does not include internal fusing.
  • Environment: Ensure the installation area is free from excessive vibration and within the specified temperature and humidity ranges.

FAQ

What is the 1746-OW16?

The 1746-OW16 is a 16-point discrete relay output module used with the SLC 500 programmable logic controller family to interface with field devices.

Can I mix AC and DC voltages on the same module?

Yes. Because the 16 channels are split into two groups of 8 with separate common terminals, you can use DC voltage for one group and AC voltage for the other simultaneously.

What is the minimum load current?

The module requires a minimum load current of 10 mA at 5V DC. If the connected device draws less than this, the relay may not switch reliably.