¿Tienes una cuenta?
Inicia sesión para finalizar tus compras con mayor rapidez.
Repuestos originales de automatización | Envío exprés a todo el mundo | Garantía de 12 meses — [Solicite presupuesto]

The Emerson DeltaV KJ3002X1-BG2 (12P1731X082) is a high-precision 8-channel analog input module designed for the DeltaV Scalable Process System. This module is specifically engineered to interface with thermocouple and millivolt (mV) sensors, providing reliable data acquisition for critical process monitoring in demanding industrial environments, including power generation, petrochemical refining, and metallurgy. It supports high-resolution temperature sensing to help maintain process stability and minimize downtime.
The KJ3002X1-BG2 features energy-limiting circuitry designed for use in Zone 2 hazardous atmospheres. It incorporates a mechanical rotary keying system, requiring the associated terminal block to be set to position B2 to ensure correct hardware compatibility. The module supports Removal and Insertion Under Power (RIUP) when used with compatible DeltaV power supplies, provided that primary circuit inductance is managed appropriately. Field power should be disconnected at the terminal level prior to physical extraction to maintain circuit integrity.
| Model | KJ3002X1-BG2 |
| Part Number | 12P1731X082 |
| Input Types | Thermocouple, Millivolt (mV) |
| LocalBus Power | 12 VDC at 350 mA |
| Field Circuit Rating | 5.5 VDC at 0.6 mA per channel |
| Operating Temperature | 0 to 60 deg C |
| Relative Humidity | 5 to 95% Non-Condensing |
| Ingress Protection | IP 20 |
| Terminal Keying | Position B2 |
| Shock Resistance | 10g 1/2 Sinewave for 11 msec |
| Vibration Resistance | 1mm P-P (5-16Hz); 0.5g (16-150Hz) |
| Airborne Contaminants | ISA-S71.04-1985 Class G3 |
The module is certified for use in Zone 2 hazardous areas (II 3 G, EEx nL IIC T4) per Nemko 02ATEX431U.
Is field calibration required for this module?
No, the KJ3002X1-BG2 is factory calibrated and does not require field calibration.
Can this module be removed while the system is powered?
Yes, it supports RIUP (Removal and Insertion Under Power), provided that field power is disconnected at the terminal block and system inductance requirements are met.