Emerson KL4201X1-BA1 DeltaV CHARM Baseplate

Emerson KL4201X1-BA1 DeltaV CHARM Baseplate

Description

The Emerson KL4201X1-BA1 is a critical hardware component within the DeltaV Electronic Marshalling system. This CHARM Baseplate provides the physical and electrical mounting infrastructure for Characterization Modules (CHARMs), enabling flexible...

17 la gente está viendo esto ahora mismo

DisponibilidadBajas existencias: quedan 10

SKU: KL4201X1-BA1
Proveedora: Emerson

Envíos y devoluciones

Entrega confiable a nivel mundial

  • Transportistas: Envíos a través de DHL, FedEx, UPS o USPS .
  • Envío: Los pedidos se procesan en 1-2 días hábiles y se envían dentro de 3-5 días hábiles .
  • Seguimiento: Detalles completos de seguimiento proporcionados por correo electrónico después del envío.

Garantía de devolución de dinero de 30 días

  • Garantía: período de devolución de 30 días para productos en stock y sellados de fábrica.
  • Condición: Los artículos deben estar sin abrir, sin usar y en su embalaje original.
  • Autenticidad: Garantizamos hardware 100% original y auténtico.

¿Necesitas más información? Consulta nuestra Política de envíos y reembolsos completa.

Autenticidad y garantía

  • Garantía genuina: Suministramos únicamente piezas de automatización industrial 100% originales, nuevas y selladas de fábrica .
  • Cobertura total: cada componente está respaldado por una garantía integral de 12 meses a partir de la fecha de compra.
  • Trazabilidad: Todos los productos se entregan con documentación original de fábrica y accesorios para un pleno cumplimiento industrial.

Soporte técnico y abastecimiento

  • Asistencia de expertos: Nuestro equipo técnico ofrece consulta gratuita para ayudarle a verificar la compatibilidad de los sistemas DCS y PLC.
  • Abastecimiento de piezas raras: nos especializamos en componentes obsoletos y difíciles de encontrar de Allen-Bradley, Siemens, ABB, HIMA y más.
  • Consultas al por mayor: contáctenos en pambo@5gplc.com para obtener precios por volumen o cotizaciones de proyectos personalizados.
Ver todos los detalles

Description

The Emerson KL4201X1-BA1 is a critical hardware component within the DeltaV Electronic Marshalling system. This CHARM Baseplate provides the physical and electrical mounting infrastructure for Characterization Modules (CHARMs), enabling flexible I/O mapping without the need for traditional cross-marshalling wires. It is designed for large-scale industrial automation, including oil and gas, petrochemical, and mining sectors, facilitating a decentralized I/O architecture that reduces installation complexity and optimizes cabinet space.

Features

  • Supports DeltaV Electronic Marshalling architecture.
  • Distributes 6.3 VDC CHARM Bus power and 24 VDC Field Circuit power.
  • Ruggedized design for G3 harsh environment compliance.
  • Supports high-density I/O configurations.
  • Compatible with standard DeltaV S-Series CHARM modules.

Applications

This baseplate is used in distributed control systems (DCS) to streamline field wiring. It is ideal for environments requiring high reliability, such as refineries, chemical processing plants, and offshore platforms where space-saving and simplified maintenance are critical.

Technical Specifications

Model KL4201X1-BA1
Brand Emerson
Series DeltaV S-Series / CHARMs
CHARM Bus Power 6.3 VDC at 4 A
Field Circuit Power 24 VDC at 10 A
Operating Temperature -40 to +70 deg C
Relative Humidity 5 to 95 percent Non-Condensing
Hazardous Area Ratings II 3G Ex ec IIC Gc; CL. I Div. 2 GP. A,B,C,D; CL. I Zone 2 AEx/Ex ec IIC Gc
Certifications FM19ATEX0173U, IECEx FMG 12.0019U, FM21UKEX0017U
Airborne Contaminants ISA-S71.04-1985 Class G3
Shock Resistance 10g 1/2 Sinewave for 11 msec
Vibration Resistance 1 mm Peak to Peak (2 to 13.2 Hz); 0.7g (13.2 to 150 Hz)

Installation Guidelines

  • Ensure the system is powered down before installing or removing the baseplate or any attached CHARM modules.
  • Verify that the installation environment is non-hazardous before performing maintenance or module replacement.
  • Mount the baseplate securely on a standard DIN rail or panel as specified by DeltaV cabinet documentation.
  • Ensure proper grounding of the baseplate to the cabinet chassis to maintain EMI/EMC integrity.
  • Route field wiring according to local electrical codes for Class I Division 2 / Zone 2 hazardous areas.
  • Maintain adequate ventilation around the baseplate to ensure operation within the specified -40 to +70 deg C range.

FAQ

Is this baseplate user-serviceable?

No, the KL4201X1-BA1 contains no user-serviceable parts and does not require calibration. Any failure typically requires a full unit replacement.

Can this be used in hazardous areas?

Yes, it is rated for use in Class I Division 2 and Zone 2 hazardous locations, provided it is installed in accordance with the relevant ATEX, IECEx, and UKEX certifications.