Configured for specialized point-to-point data exchange, the Yokogawa ALR111-S50 (ALR111) Serial Communication Module provides direct physical electrical execution for RS-232C-based device interfacing within CENTUM VP and ProSafe-RS control architectures.
| Parameter | Specification |
|---|---|
| Model | ALR111-S50 |
| Brand | Yokogawa |
| Interface | 2 x RS-232C Ports |
| Transmission Speed | 1200 to 38,400 bps |
| Transmission Distance | Max 15 m |
| Connector Type | D-sub 9-pin (Female x 2) |
| Current Consumption | 0.5 A |
| Weight | 0.3 kg |
The ALR111-S50 utilizes a start-stop synchronization method for binary data transmission. It is engineered for deterministic serial communication, supporting various baud rates and parity configurations to match specific field instrument requirements. Due to the inherent nature of the RS-232C standard, communication is limited to a 15-meter transmission distance to ensure signal voltage levels remain within valid logical thresholds, preventing bit-errors caused by line capacitance and attenuation.
Q: Does the ALR111-S50 support full-duplex communication?
A: No, the module is specifically configured for half-duplex communication, meaning data can be transmitted or received, but not simultaneously, following the logic requirements of the connected field subsystem.
Q: Can this module be used in hazardous locations?
A: The "S50" suffix denotes that this module does not have explosion protection. It must be installed in a non-hazardous, controlled environment or shielded appropriately if required by local process safety regulations.