Genuine Automation Parts | Worldwide Express Delivery | 12-Month Warranty — [GET A QUOTE]

Configured for precision actuator control in CENTUM VP and related process control platforms, the YOKOGAWA ASI533-S00 (ASI533 Analog Output Module) provides direct physical/electrical execution of 4-20 mA DC control signals to field-level process hardware.
| Parameter | Specification |
|---|---|
| Model | ASI533-S00 |
| Brand | YOKOGAWA |
| Origin | japan |
| Weight | 0.30 kg |
| Dimensions | 282 mm x 210 mm x 20 mm |
| Operating Temp | Not specified |
| Power Consumption | 150 mA (5 V DC) / 350 mA (24 V DC) |
| Output Channels | 8 channels |
| Signal Type | 4-20 mA DC |
| Accuracy | +/- 48 uA |
The ASI533-S00 module integrates directly into DCS process loops utilizing the 4-20 mA HART loop protocol, enabling intelligent status monitoring of connected valves and actuators. To ensure signal integrity, each of the 8 channels features individual isolation with a withstanding voltage of 1500 V AC between the output loop and internal circuit logic. This robust isolation design prevents electrical noise propagation and ground loops, maintaining the accuracy of the control signal even in high-density process environments.
Q: Does the ASI533-S00 support HART pass-through communication?
A: Yes, the module supports HART communication protocols, allowing for the transmission of device diagnostics and configuration data alongside the primary 4-20 mA control signal. Ensure that the host controller software is configured to recognize the HART frame format.
Q: What is the impact of ambient temperature fluctuations on module accuracy?
A: The module is calibrated for an accuracy of +/- 48 uA at 23 deg C. The thermal drift is specified at +/- 16 uA per 10 deg C change in ambient temperature. Ensure the cabinet environment is maintained within stable thermal limits to maximize output precision.