The Bently Nevada 190501-12-99-04 is a specialized Velomitor CT (Cooling Tower) velocity transducer engineered for low-frequency vibration monitoring. This piezoelectric sensor is optimized to measure casing vibration velocity on rotating machinery, specifically air-cooled heat exchangers and cooling tower fan assemblies operating at speeds of 90 RPM or higher.
Features
- Low-frequency response optimized for cooling tower and fan assembly monitoring.
- Measures casing vibration velocity to detect mechanical faults in rotating equipment.
- Integrated 32-foot cable for simplified field installation.
- Includes mounting hardware (12 Plate Stud 3/8-in 24 to M8x1).
- Hazardous area certified for Class I, Division 1 and Class I, Zone 0/1 environments.
Applications
- Power Generation: Protection for cooling tower fans and auxiliary cooling systems.
- Oil & Gas: Monitoring critical cooling systems and heat exchangers.
- Petrochemical & Chemical: Ensuring reliability of large-scale air-cooled heat exchangers.
- Wastewater Treatment: Continuous vibration monitoring for aeration and cooling fan assemblies.
Technical Specifications
| Model |
190501-12-99-04 |
| Sensitivity |
3.94 mV/mm/s (100 mV/in/s) +/- 5% |
| Transverse Response |
Less than 5% of axial sensitivity |
| Mounting |
Plate Stud 3/8-in 24 to M8x1 |
| Cable |
Included 32-foot integral cable |
| Hazardous Area Approval |
CSA/NRTL/C (Class I, Div 1); ATEX/IECEx/CSA (Class I, Zone 0/1) |
Installation Guidelines
-
Mounting: Use the provided 3/8-in 24 to M8x1 stud. Apply a thread sealant such as Loctite 242 to the mounting stud to prevent loosening caused by continuous low-frequency oscillations.
-
Hazardous Areas: When installing in Class I, Div 1 or Zone 0/1 environments, you must utilize an intrinsically safe (IS) galvanic isolator or zener barrier to ensure compliance.
-
Handling: As a precision piezoelectric sensor, avoid dropping or subjecting the transducer to high-impact shocks during installation.
-
Cabling: Route the integral 32-foot cable away from high-voltage power lines to minimize electromagnetic interference (EMI).
FAQs
What is the primary purpose of the 190501-12-99-04?
This transducer is designed to monitor casing vibration on low-speed rotating equipment, specifically cooling tower fans and air-cooled heat exchangers that operate at 90 RPM or above.
What is the sensitivity of this sensor?
The sensor features a standard sensitivity of 3.94 mV/mm/s (100 mV/in/s) with a tolerance of +/- 5%.
Does this model require specific safety barriers?
Yes, for installations in hazardous locations (Class I, Div 1 or Zone 0/1), an approved intrinsically safe galvanic isolator or zener barrier is required.