Genuine Automation Parts | Worldwide Express Delivery | 12-Month Warranty — [GET A QUOTE]

The BMXAMI0810 is a high-precision analog input module for the Schneider Electric Modicon X80 platform, compatible with Modicon M580 and Modicon M340 control systems.
It provides 8 fully isolated analog input channels for high-accuracy process monitoring. The module supports multiple voltage and current signal ranges and uses a 16-bit A/D converter with digital filtering to improve measurement stability and noise rejection in harsh industrial environments.
The BMXAMI0810 is widely used in critical process control applications requiring precise real-time data acquisition and strong protection against electrical interference.
| Parameter | Specification |
|---|---|
| Model | BMXAMI0810 |
| Platform | Modicon X80 / M580 / M340 |
| Input Channels | 8 |
| Resolution | 16-bit (15 bits + sign) |
| Voltage Input Impedance | ≥ 10 MΩ |
| Current Input Impedance | 250 Ω |
| Read Cycle | 9 ms (all channels) |
| Fast Cycle Mode | 1 ms + 1 ms per channel |
| Accuracy | ±0.1% FS @ 25°C |
| Digital Filtering | Configurable |
| Power Consumption | 150 mA @ 3.3 V DC |
Oil and gas process monitoring
Chemical processing plants
Power generation control systems
Long-distance distributed sensor networks
Ideal for high-resolution measurement of pressure, flow, and temperature in large industrial facilities.
Q1: What is the benefit of 1500 V isolation?
It protects the controller from voltage surges and eliminates ground loop measurement errors between distributed sensors.
Q2: Which terminal block is required?
The module requires a 20-way removable terminal block, typically BMXFTB2000 (screw type) or BMXFTB2010 (spring clamp type).