Skip to product information
1 of 3

C65H-DCC6A DC Miniature Circuit Breaker 10kA

C65H-DCC6A DC Miniature Circuit Breaker 10kA

Product Overview

The Schneider Electric C65H-DCC6A functions as a high-performance miniature circuit breaker (MCB) purpose-built for direct current (DC) applications. As a core component of the Multi 9 C65H series, this 2-pole...

29 people are viewing this right now

AvailabilityLow stock: 94 left

SKU: C65H-DCC6A
Vendor: Schneider

Shipping & Returns

Reliable Worldwide Delivery

  • Carriers: Shipped via DHL, FedEx, UPS, or USPS.
  • Dispatch: Orders processed in 1-2 business days and dispatched within 3-5 business days.
  • Tracking: Full tracking details provided via email upon shipment.

30-Day Money-Back Guarantee

  • Guarantee: 30-day return window for in-stock, factory-sealed products.
  • Condition: Items must be unopened, unused, and in original packaging.
  • Authenticity: We guarantee 100% original and authentic hardware.

Need more details? Read our fullShipping PolicyandRefund Policy.

Authenticity & Warranty

  • Genuine Guarantee: We supply only 100% original, brand-new, and factory-sealed industrial automation parts.
  • Full Coverage: Every component is backed by a 12-month comprehensive warranty from the date of purchase.
  • Traceability: All products come with original factory documentation and accessories for full industrial compliance.

Technical Support & Sourcing

  • Expert Assistance: Our technical team provides free consultation to help you verify compatibility for DCS and PLC systems.
  • Rare Part Sourcing: Specializing in obsolete and hard-to-find components from Allen-Bradley, Siemens, ABB, HIMA, and more.
  • Bulk Inquiries: Contact us at pambo@5gplc.com for volume pricing or customized project quotes.
View full product details

Product Overview

The Schneider Electric C65H-DCC6A functions as a high-performance miniature circuit breaker (MCB) purpose-built for direct current (DC) applications. As a core component of the Multi 9 C65H series, this 2-pole breaker provides essential overload and short-circuit protection for low-voltage DC networks. It utilizes a thermal-magnetic tripping mechanism with a C-curve characteristic, specifically calibrated to handle moderate inrush currents while maintaining tight protection for sensitive electronics. We supply this unit as 100% Brand New and Original, ensuring critical safety for solar photovoltaic (PV) arrays, telecommunications infrastructure, and battery energy storage systems (BESS).

Technical Specifications

Parameter Specification
Manufacturer Schneider Electric
Model Number C65H-DCC6A
Number of Poles 2P
Rated Current ($I_n$) 6 A
Tripping Curve C Curve
Rated Operational Voltage ($U_e$) 250 V DC
Breaking Capacity ($I_{cu}$) 10 kA at 250 V DC (IEC 60947-2)
Impulse Withstand Voltage ($U_{imp}$) 5 kV
Mechanical Endurance 20,000 cycles
Electrical Endurance 10,000 cycles
Mounting Support 35 mm symmetrical DIN rail
Terminal Capacity 1 mm² to 25 mm² (Rigid cables)
Operating Temperature -30 °C to +70 °C
Standards IEC 60947-2, IEC 60898-2

Engineering Advantages

  • Superior Arc Suppression: Unlike standard AC breakers, the C65H-DCC6A features specialized internal permanent magnets to pull DC arcs into the chutes. This design ensures rapid quenching of direct current arcs, which are naturally more difficult to extinguish than AC.

  • Optimized Renewable Integration: The C-curve characteristic perfectly balances the requirements of solar inverters and battery chargers. It prevents nuisance tripping during initial capacitor charging while responding instantaneously to short-circuit faults in the DC bus.

  • Industrial Environmental Resilience: The module operates reliably across an extended temperature range from -30°C to +70°C. This thermal stability makes it ideal for outdoor-rated PV combiner boxes and unconditioned telecommunication shelters.

  • Compact DIN-Rail Efficiency: Occupying only 36mm of rail width, this breaker maximizes space within crowded control panels. The modular format allows for rapid integration with other Multi 9 accessories, such as auxiliary contacts and shunt trips.

FAQs

  • Does the C65H-DCC6A require specific polarity during wiring?

    Yes. DC circuit breakers are polarity sensitive due to the magnetic arc-quenching design. You must follow the terminal markings (+/-) indicated on the front or side of the device to ensure the arc is correctly directed into the arc chute during a fault. Failure to observe polarity can damage the breaker.

  • Can I use this 250V DC breaker for higher voltage solar strings?

    This specific model is rated for 250V DC. If your solar array output or battery bank exceeds this operational voltage, you must utilize a higher-rated model or connect multiple poles in series as per Schneider’s technical wiring diagrams to increase the dielectric strength.

  • What is the breaking capacity of this unit?

    The C65H-DCC6A provides a high breaking capacity of 10 kA. This rating ensures the breaker can safely interrupt high-magnitude fault currents without exploding or welding the contacts, protecting the downstream cables and expensive DC equipment.