Emerson DeltaV KJ3002X1-BG2 12P1731X032 8-Channel Thermocouple/mV Input Module

Emerson DeltaV KJ3002X1-BG2 12P1731X032 8-Channel Thermocouple/mV Input Module

Description

The Emerson DeltaV KJ3002X1-BG2 (also identified by assembly part number 12P1731X032 and model VE4003S5B1) is a high-precision, 8-channel analog input module designed for the DeltaV Scalable Process System. This module...

20 people are viewing this right now

AvailabilityLow stock: 6 left

SKU: KJ3002X1-BG2 12P1731X032
Vendor: Emerson

Shipping & Returns

Reliable Worldwide Delivery

  • Carriers: Shipped via DHL, FedEx, UPS, or USPS.
  • Dispatch: Orders processed in 1-2 business days and dispatched within 3-5 business days.
  • Tracking: Full tracking details provided via email upon shipment.

30-Day Money-Back Guarantee

  • Guarantee: 30-day return window for in-stock, factory-sealed products.
  • Condition: Items must be unopened, unused, and in original packaging.
  • Authenticity: We guarantee 100% original and authentic hardware.

Need more details? Read our fullShipping PolicyandRefund Policy.

Authenticity & Warranty

  • Genuine Guarantee: We supply only 100% original, brand-new, and factory-sealed industrial automation parts.
  • Full Coverage: Every component is backed by a 12-month comprehensive warranty from the date of purchase.
  • Traceability: All products come with original factory documentation and accessories for full industrial compliance.

Technical Support & Sourcing

  • Expert Assistance: Our technical team provides free consultation to help you verify compatibility for DCS and PLC systems.
  • Rare Part Sourcing: Specializing in obsolete and hard-to-find components from Allen-Bradley, Siemens, ABB, HIMA, and more.
  • Bulk Inquiries: Contact us at pambo@5gplc.com for volume pricing or customized project quotes.
View full product details

Description

The Emerson DeltaV KJ3002X1-BG2 (also identified by assembly part number 12P1731X032 and model VE4003S5B1) is a high-precision, 8-channel analog input module designed for the DeltaV Scalable Process System. This module is engineered for thermocouple and millivolt (mV) signal acquisition, providing reliable temperature monitoring in critical industrial applications such as boilers, furnaces, and chemical reactors. It features integrated cold junction compensation (CJC) and high-resolution data conversion to ensure accurate process control and rapid response to thermal changes.

Features

  • 8 Independent Channels: Each channel is independently configurable to support various thermocouple types (J, K, T, E, R, S, B, N) and low-level voltage signals (-100 to +100 mV).
  • Integrated CJC: Cold junction compensation is built directly into the terminal block to maintain measurement precision across varying ambient temperatures.
  • Advanced Diagnostics: Includes built-in sensor-error detection, such as open-thermocouple burnout detection, for immediate field-level failure identification.
  • Robust Design: Rated for harsh environments with ISA-S71.04-1985 Class G3 compliance and wide operating temperature range.
  • Galvanic Isolation: Provides electrical isolation between field signals and system logic to protect sensitive control components.

Applications

This module is widely used in process automation environments requiring high-density temperature monitoring, including oil and gas refining, power generation, pharmaceutical manufacturing, and chemical processing plants.

Technical Specifications

Model KJ3002X1-BG2 (VE4003S5B1)
Assembly Number 12P1731X032
Input Channels 8
Input Types Thermocouple (B, E, J, K, N, R, S, T), mV (-100 to +100 mV)
Resolution 16-bit
Local Bus Power 12 VDC at 150 mA
Operating Temperature -40 to +70 deg C
Relative Humidity 5 to 95 percent (Non-Condensing)
Hazardous Area Rating ATEX II 3G, Class I Div 2, Ex nA IIC Gc

Installation Guidelines

  • ESD Precautions: Always handle the module using proper electrostatic discharge (ESD) protection, such as a grounded wrist strap, to prevent damage to sensitive internal circuitry.
  • Power Down: Ensure the DeltaV carrier power is disconnected before inserting or removing the module from the I/O carrier.
  • Terminal Block Seating: Ensure the terminal block is fully seated and secured to the module to maintain proper cold junction compensation contact.
  • Wiring: Use shielded twisted-pair cabling for thermocouple signals to minimize electromagnetic interference (EMI). Ensure proper grounding of shields at the cabinet entry point.
  • Environment: Ensure the module is installed in a location that meets the specified temperature and humidity requirements and is protected from direct exposure to corrosive elements.

FAQ

Q: Can I mix different thermocouple types on the same module?
A: Yes, each of the 8 channels is independently configurable, allowing for a mix of different thermocouple types or mV signals on a single card.

Q: Does this module require external field power?
A: No, the module does not require bussed field power for sensor excitation.

Q: Is this module suitable for hazardous locations?
A: Yes, it is rated for Zone 2/Division 2 environments (ATEX II 3G, Class I Div 2, Ex nA IIC Gc).