The IC693PBM200 is a high-performance communication module designed for the GE Fanuc Series 90-30 Programmable Logic Controller (PLC) platform. As a PROFIBUS DP Master module, it enables the integration of the Series 90-30 system into complex fieldbus networks, facilitating seamless data exchange with up to 125 PROFIBUS DP slave devices. This module is essential for applications requiring robust, high-speed remote I/O communication and multi-vendor device interoperability.
Features
- Compatible with all Series 90-30 baseplates (CPU, expansion, or remote).
- Supports up to 125 PROFIBUS DP slave devices.
- Configurable data transfer capacity up to 244 bytes of input and 244 bytes of output per slave.
- Supports standard PROFIBUS transmission rates from 9.6 Kbaud up to 12 MBaud.
- Includes one (1) RS485 PROFIBUS Master port and one (1) RS232 service port for configuration and firmware updates.
- Integrated diagnostic capabilities including slave status bit arrays, network diagnostic counters, and master diagnostic counters.
- Status monitoring via dedicated SYS and COM LEDs.
Applications
-
Automotive & Manufacturing: Synchronization of variable frequency drives (VFDs) and motor starters for conveyor systems and robotics.
-
Food & Beverage: High-speed I/O management for synchronized sorting and packaging lines.
-
Process Industry: Remote monitoring of sensors and actuators in steel, chemical, and plastic injection molding facilities.
Technical Specifications
| Model |
IC693PBM200 |
| Manufacturer |
General Electric |
| Bus Interface |
PROFIBUS DP Master |
| Backplane Current |
450 mA at 5VDC (typical) |
| Baud Rates |
9.6K, 19.2K, 93.75K, 187.5K, 500K, 1.5M, 3M, 6M, 12M |
| Max Slaves |
125 |
| Ports |
1x RS485 (Profibus), 1x RS232 (Service) |
| Tariff Code |
8537101190 |
Installation Guidelines
- Power down the PLC rack completely before inserting or removing the module to prevent electrical damage.
- The module can be installed in any slot on a Series 90-30 baseplate, excluding Slot 1, which is reserved for the CPU.
- Ensure the use of high-quality, continuous shielded PROFIBUS cabling to maintain signal integrity.
- Maintain a high-frequency ground connection within 18 inches of the module to maximize noise immunity in industrial environments.
FAQ
What is the primary function of the IC693PBM200?
It acts as a master node on a PROFIBUS-DP network, allowing a Series 90-30 PLC to act as a controller for remote I/O, drives, and other field devices.
Which software is required for configuration?
Configuration is typically performed using Proficy Machine Edition Logic Developer, version 2.6 or later.
How does the IC693PBM200 differ from the older HE693PBM101?
The IC693PBM200 provides a larger default slave status area (128 points) and organizes status bits by bus address for improved diagnostic clarity.