Genuine Automation Parts | Worldwide Express Delivery | 12-Month Warranty — [GET A QUOTE]

The FC-TSDO-1624 is a high-integrity Field Termination Assembly (FTA) for the Honeywell Safety Manager (SMS) and Safety Manager SC systems. It serves as the physical interface between digital output modules and field-side final control elements, managing 16 channels of 24 Vdc power-to-load signals.
Designed for SIL 2 and SIL 3 applications, it drives solenoid valves, relays, and motor starters while providing electrical isolation and robust industrial reliability.
| Specification | Details |
|---|---|
| Model Number | FC-TSDO-1624 |
| Equipment Type | Safe Digital Output Field Termination Assembly (FTA) |
| Channel Density | 16 independent channels |
| Nominal Output Voltage | 24 Vdc |
| Operating Voltage Range | 18–30 Vdc |
| Nominal Output Current | 2.0 A per channel |
| Maximum Response Time | < 25 ms |
| Operating Temperature | –40°C to +70°C (–40°F to +158°F) |
| Environmental Resilience | Harsh industrial and corrosive atmospheres |
The FC-TSDO-1624 is engineered for mission-critical reliability in high-risk industries. Its <25 ms response time ensures immediate actuation of safety valves and isolation devices during ESD events.
With an IP65 rating and wide operating temperature range, it can be mounted in field junction boxes or remote instrument enclosures near hazardous processes. The module prioritizes fail-safe operation, transitioning outputs to de-energized states upon faults or communication loss.
Q: Can the FC-TSDO-1624 be used in explosive atmospheres?
A: Yes, it is ATEX-certified for use in designated hazardous areas when installed per protection and enclosure requirements.
Q: Is this FTA compatible with the Safety Manager SC?
A: Yes, it is fully compatible with both legacy Safety Manager and Safety Manager SC hardware suites.