Genuine Automation Parts | Worldwide Express Delivery | 12-Month Warranty — [GET A QUOTE]

Configured for high-density process signal acquisition in distributed control system platforms, the Yokogawa NFAP135-S00 (NFAP135) Analog Input Module provides direct physical electrical execution for 16-channel analog monitoring in industrial automation environments.
| Parameter | Specification |
|---|---|
| Model | NFAP135-S00 |
| Brand | Yokogawa |
| Weight | 0.3 kg |
| Input Channels | 16 |
| Signal Range | 4-20 mA DC or 1-5 V DC |
| Compatibility | 2-wire / 4-wire transmitters |
| Isolation | Non-isolated |
| Power Supply | 5 V DC |
The NFAP135-S00 is designed for environments requiring high-precision data acquisition from standard industrial transmitters. As a non-isolated module, it is optimized for applications where loop reference points are managed at the terminal level or are common to the control system ground. The module supports both current and voltage inputs, allowing for flexible interfacing with a variety of process sensors without requiring additional signal conversion hardware.
Q: What precautions should be taken given the non-isolated nature of the module?
A: Since the 16 channels share a common ground, it is vital to ensure that no significant potential differences exist between field device grounds. If loop isolation is required to prevent ground loops or cross-channel interference, external signal isolators should be installed.
Q: Is this module capable of powering the connected transmitters?
A: The NFAP135-S00 is designed to process signals from 2-wire or 4-wire transmitters; however, the module's 5 V DC power supply is for internal logic and communication, not for driving high-current field devices. Ensure proper loop power supply design according to the transmitter's data sheet.