The 8200-205 is a high-reliability electronic overspeed protection system from the ProTech 203 series developed by Woodward, Inc.. It provides critical safety protection for steam, gas, and industrial turbines by continuously monitoring rotational speed through independent magnetic pickup (MPU) sensors.
The system uses a three-channel 2-out-of-3 voting logic architecture, ensuring that a single sensor or channel failure will not compromise safety protection. The De-Energize-to-Trip design guarantees that loss of control power or detection of abnormal conditions will automatically trigger a safe shutdown sequence.
The module is housed in a rugged NEMA 4/4X-rated enclosure, providing protection against dust, water ingress, and corrosive industrial environments. Integrated displays and keypads allow local diagnostics and parameter adjustments without external tools.
| Parameter | Specification |
|---|---|
| Model | 8200-205 |
| Series | ProTech 203 |
| Protection Logic | De-Energize-to-Trip (Fail-safe) |
| Sensing Architecture | 3 independent MPU channels (2oo3 voting) |
| Input Voltage | 220 VAC (nominal) |
| Trip Frequency Range | 250 Hz – 25 kHz |
| Sensor Compatibility | Passive magnetic pickup sensors |
| User Interface | Per-module display + keypad |
| Enclosure Rating | NEMA 4 / 4X |
| Operating Temperature | –15°C to +60°C |
| Weight | 5.93 kg |
Steam and gas turbine protection systems
Utility-scale power generation plants
Petrochemical and refinery rotating equipment protection
Mechanical drive turbine safety systems
What is De-Energize-to-Trip?
The trip relay is energized during normal operation. If overspeed or power loss is detected, the relay de-energizes to trigger shutdown, ensuring fail-safe protection.
Can trip points be adjusted during operation?
Yes, but adjustments should only be performed by authorized technicians following safety commissioning procedures.
Does it require special MPUs?
No. It supports standard passive MPU sensors within the specified frequency range.