Genuine Automation Parts | Worldwide Express Delivery | 12-Month Warranty — [GET A QUOTE]

The Honeywell 900P01-0201 is the primary power supply module for the ControlEdge HC900 controller racks. This module converts standard AC power (120/240 VAC) to the regulated DC voltages required to power the CPU, expansion processors, and I/O modules. It ensures clean and stable power for high-precision industrial automation tasks.
| Parameter | Specification |
|---|---|
| Model Number | 900P01-0201 |
| Manufacturer | Honeywell |
| Input Voltage | 120/240 VAC (nominal), 50/60 Hz |
| Input Voltage Range | 90 to 264 VAC |
| Output Power | Powers the HC900 backplane logic |
| Dimensions | 18 cm x 11.5 cm x 6.3 cm |
| Weight | 1.5 kg |
| Mounting | Dedicated power slot in HC900 racks |
Universal AC Input
The 900P01-0201 supports a wide input voltage range from 90 to 264 VAC, making it suitable for global deployments without needing region-specific transformers or power supply variants.
Integrated Surge Protection
Internal circuitry offers surge protection, shielding the controller and I/O modules from voltage spikes and transients, ensuring reliable performance and extending hardware lifespan.
Efficient Heat Dissipation
Designed with a ventilated structure, the module effectively manages thermal loads, ensuring stable operation even with high-current I/O modules in populated racks. It functions within a 0°C to 60°C temperature range.
Redundant Configuration Support
In redundant rack configurations (e.g., 900RR0 series), two modules can operate in parallel. If one fails, the other immediately takes over, ensuring bumpless operation without interrupting processes.
Does this power supply also power field-side instruments?
No, the 900P01-0201 powers the internal rack components and I/O circuitry. A separate 24 VDC power supply is required for field-side devices like transmitters, actuators, and solenoids.
How do I verify if the power supply is functioning correctly?
The status LED on the front panel shows a green light when the input voltage is within range and power is successfully delivered to the backplane.
Can I replace a 900P01-0101 with this 0201 model?
Yes, the 900P01-0201 supersedes the older 900P01-0101 model, maintaining the same physical footprint and electrical interface for seamless integration and hardware upgrades.
What is the condition of the unit?
This unit is 100% Brand New, unused, and ships in its original Honeywell factory-sealed packaging to ensure compliance with all technical and safety standards.