Genuine Automation Parts | Worldwide Express Delivery | 12-Month Warranty — [GET A QUOTE]

The Woodward 5464-013 is a high-precision RTD interface module designed for MicroNet and MicroNet Plus control platforms. It enables accurate thermal monitoring of critical turbine and engine components like bearing temperatures, winding temperatures, and lube oil systems. By converting low-level resistance signals from 100-ohm platinum RTDs into digital data, it ensures reliable thermal protection logic and minimal signal drift.
This module features eight independent channels, each with advanced filtering to reject EMI and line noise, ensuring accuracy in high-voltage environments. It also has built-in diagnostic capabilities to detect sensor faults, like open circuits or shorted wiring, for proactive protection.
| Specification | Details |
|---|---|
| Model Number | 5464-013 |
| Module Type | RTD Input Interface (Analog) |
| Number of Channels | 8 Independent Inputs |
| Sensor Compatibility | 100-ohm Platinum RTDs (European or American Curves) |
| Measurement Accuracy | ±1.1°C (at 25°C ambient) |
| Input Resolution | 12-bit to 14-bit A/D conversion |
| Excitation Current | 2 mA (internally provided) |
| Isolation | Field-to-Logic isolation |
| Fault Detection | Automatic sensing for open/short sensor conditions |
| Temperature Tracking | Linearized data transmission to CPU |
| Operating Temperature | -10°C to +60°C (Internal rack ambient) |
| Weight | 2.4kg |
Commonly used in power generation for monitoring generator stator windings and thrust bearing temperatures, and in compressor stations for monitoring interstage gas temperatures and lubricant thermal stability.
Does this module support 3-wire or 4-wire RTD configurations?
The 5464-013 supports 3-wire RTD configurations, ensuring accuracy over long distances by compensating for lead-wire resistance.
Can I mix different RTD types on a single module?
The module is configured for a specific RTD curve via Woodward GAP® software. Although individual channel ranges can be defined, the same RTD material (e.g., Pt100) should be used across all channels.
How does the module handle high-frequency vibration on the sensor lines?
The module includes analog and digital filtering to suppress high-frequency noise commonly found in industrial machinery environments.