Genuine Automation Parts | Worldwide Express Delivery | 12-Month Warranty — [GET A QUOTE]

The Woodward 8440-2084, also cataloged as the easYgen-3400XT-P1 Genset Controller, operates as a dedicated hardware component for advanced paralleling, load sharing, and engine protection within complex multi-generator automation networks. Designed without an integrated front display for rear panel mounting, the unit executes direct electrical measurement of 50 Vac to 650,000 Vac systems across a 40 Hz to 85 Hz frequency spectrum, interfacing with up to 32 generator controllers and 16 LS-5 circuit breakers across shared CAN bus links.
| Parameter | Specification |
|---|---|
| Model | 8440-2088 (easYgen-3400XT-P1) |
| Brand | Woodward |
| Origin | USA |
| Weight | 2.5 kg |
| Dimensions | 282 x 216 x 96 mm |
| Operating Temp | -20 deg C to +70 deg C |
| Power Consumption | 12/24 VDC nominal (8 to 40 VDC operating range) |
| CT Input Rating | 1 A / 5 A secondary |
| Voltage Measurement | 50 Vac to 650,000 Vac |
| Frequency Range | 40 Hz to 85 Hz |
| Display | None (remote panel/PC operated) |
| Mounting | Rear panel-mounted |
| Enclosure Rating | Metal housing, IP20 (IP54 with optional cover) |
The Woodward 8440-2084 processes continuous current transformer (CT) inputs rated at 1 A or 5 A to evaluate real-time active and reactive power distribution across networked gensets. Internal processing loops dynamically calculate fuel governor and automatic voltage regulator (AVR) bias commands, optimizing actuator loop feedback response during synchronization, ramp loading, and bus decoupling operations to maintain grid frequency stability.
Q: How is local parameter monitoring conducted given that the 8440-2084 lacks an integrated LCD screen?
A: Operator interface and monitoring are executed via external CAN-connected remote panels (such as the RP-3000XT) or directly through a PC utilizing Woodward ToolKit software over serial or USB communication ports.
Q: What power supply operating range is supported by the internal DC power stage?
A: The main board is rated for 12 VDC or 24 VDC nominal system power, accepting a wide continuous input window from 8 VDC to 40 VDC to withstand severe engine cranking voltage drops.
Q: How many networked units and circuit breakers can be synchronized in a single system loop?
A: The internal communications logic supports deterministic load-sharing parameters across a network topology containing up to 32 generators and up to 16 LS-5 circuit breaker control units.