Genuine Automation Parts | Worldwide Express Delivery | 12-Month Warranty — [GET A QUOTE]

Configured for power distribution management in CENTUM VP control network, the Yokogawa AEP7D-15 (AEP7D Primary Power Supply Bus Unit) provides direct physical electrical distribution execution. The unit facilitates the routing of primary power to associated instrumentation loops while maintaining isolation standards within the chassis assembly.
| Parameter | Specification |
|---|---|
| Model | AEP7D-15 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 0.8 kg (estimated) |
| Dimensions | 132 mm x 100 mm x 225 mm |
| Operating Temp | 0 to 50 deg C |
| Power Consumption | 100 - 120 V AC |
| Withstanding Voltage | 1500 V AC |
| Max. Input Current (Unit) | 20 A |
| Max. Input Current (Port) | 6 A |
The AEP7D series units are engineered to support stable 4-20 mA HART loop protocol environments by ensuring consistent voltage delivery to field-side components. The architecture supports channel-to-channel isolation to prevent ground loops and electrical noise propagation. When integrating into a DCS cabinet, the power distribution bus handles the conversion and allocation of power while maintaining internal thermal stability within the control cabinet environment.
Q: Does the AEP7D-15 support hot-swapping under load?
A: No, the primary power supply bus unit is not designed for hot-swapping. Input power must be physically disconnected and verified as zero potential before extraction to prevent contact arcing.
Q: What is the maximum acceptable voltage fluctuation for the input side?
A: The input is rated for 100 - 120 V AC. Operations exceeding these nominal limits may trigger the internal protection circuitry or lead to degradation of the bus components.