Skip to product information
1 of 3

YOKOGAWA ALF111-S00 S1 Foundation Fieldbus FF-H1 Communication Module

YOKOGAWA ALF111-S00 S1 Foundation Fieldbus FF-H1 Communication Module

The YOKOGAWA ALF111-S00 S1, also cataloged as the ALF111 Communication Module, operates as a dedicated hardware component for fieldbus network integration within Centum VP distributed control system platforms. This module...

24 people are viewing this right now

AvailabilityIn stock

SKU: ALF111-S00 S1
Vendor: Yokogawa

Shipping & Returns

Reliable Worldwide Delivery

  • Carriers: Shipped via DHL, FedEx, UPS, or USPS.
  • Dispatch: Orders processed in 1-2 business days and dispatched within 3-5 business days.
  • Tracking: Full tracking details provided via email upon shipment.

30-Day Money-Back Guarantee

  • Guarantee: 30-day return window for in-stock, factory-sealed products.
  • Condition: Items must be unopened, unused, and in original packaging.
  • Authenticity: We guarantee 100% original and authentic hardware.

Need more details? Read our fullShipping PolicyandRefund Policy.

Authenticity & Warranty

  • Genuine Guarantee: We supply only 100% original, brand-new, and factory-sealed industrial automation parts.
  • Full Coverage: Every component is backed by a 12-month comprehensive warranty from the date of purchase.
  • Traceability: All products come with original factory documentation and accessories for full industrial compliance.

Technical Support & Sourcing

  • Expert Assistance: Our technical team provides free consultation to help you verify compatibility for DCS and PLC systems.
  • Rare Part Sourcing: Specializing in obsolete and hard-to-find components from Allen-Bradley, Siemens, ABB, HIMA, and more.
  • Bulk Inquiries: Contact us at pambo@5gplc.com for volume pricing or customized project quotes.
View full product details

The YOKOGAWA ALF111-S00 S1, also cataloged as the ALF111 Communication Module, operates as a dedicated hardware component for fieldbus network integration within Centum VP distributed control system platforms. This module provides direct physical/electrical execution for connecting FOUNDATION Fieldbus H1 segments to the control network, enabling seamless data exchange between the host controller and field-mounted instruments.

Suffix Breakdown & Model Matrix

  • ALF111: Base communication module model for Foundation Fieldbus H1 interface.
  • -S00: Standard hardware revision for direct integration into Yokogawa fieldbus I/O modules.
  • S1: Specific product iteration/manufacturing revision level.

Hardware Specifications

Parameter Specification
Model ALF111-S00 S1
Brand Yokogawa
Origin Japan
Weight 0.3 kg
Dimensions 12.7 cm x 2.5 cm x 12.7 cm
Operating Temp -20 to 70 deg C
Power Consumption 1.5 W (Typical)
Interface Type Foundation Fieldbus FF-H1
Segment Connection 1 Segment

FOUNDATION Fieldbus Connectivity and Process Control

The ALF111-S00 S1 utilizes specialized circuitry to manage FF-H1 segment communication, ensuring deterministic data exchange between the field instrumentation and the DCS backplane. The module provides internal galvanic isolation to protect the control system from segment-side electrical surges and noise. It supports standard FOUNDATION Fieldbus protocol stacks, facilitating real-time process monitoring, loop control, and device diagnostics for connected pressure, temperature, and flow transmitters.

Frequently Asked Questions

Q: Is the ALF111 module capable of powering the H1 fieldbus segment directly?

A: No, the ALF111 performs the communication interface duties; a separate fieldbus power supply and power conditioner are required to provide the necessary DC voltage to the H1 segment.

Q: Can this module be hot-swapped while the fieldbus segment is active?

A: Yes, the module supports hot-swapping within the Yokogawa control station, provided that the DCS configuration supports online module replacement and the fieldbus power is maintained separately to prevent segment communication loss.

Field Installation Guidelines

  • Verify that the segment impedance is correctly matched by installing appropriate terminators at both ends of the H1 fieldbus segment to prevent signal reflections.
  • Ensure the module is fully seated into the designated backplane slot and the latching mechanism is engaged to maintain constant electrical contact.
  • Use shielded, twisted-pair cabling for fieldbus segments and ensure the cable shield is grounded at a single point to mitigate electromagnetic interference.
  • Maintain a minimum clearance around the module to allow for proper thermal dissipation during operation within the specified temperature range.
  • Perform a visual check of the status LEDs after system power-up to confirm the module has established logical communication with the segment devices.